Get a Quote
← All articles

How to Calculate Pumping Head and Required Water Pressure

A practical guide to calculating pumping head for boreholes: static lift, tank height, friction losses and pressure requirements, with a worked example and pressure conversions.

By Quantum Geoconsultants pump installation teamUpdated 19 November 20262 min read
TopsoilLava flowOlder lavas & tuffsStatic water level (pump off) Pumping water level ◀ Submersible pump & motor ◀ Screen below the pump Pump sized from test pumping

⚙️ Borehole Pumps & Solar: a technical article by the Quantum Geoconsultants pump installation team.

To choose a pump, you need to know how much “push” it must provide. This is the pumping head, measured in metres of water. This article explains how to calculate it and how it relates to water pressure.

Head and pressure

Head is the height a pump can lift water. Pressure and head are related:

So a tap needing 2 bar requires about 20 m of head at that point.

Components of pumping head

1. Lift from the water level

The vertical distance from the dynamic water level in the borehole to ground level.

2. Elevation to the delivery point

The vertical height from ground at the borehole to the tank inlet or highest delivery point, including tank stand height and any rise in ground level along the route.

3. Friction losses

Energy lost in the rising main, delivery pipe, valves and fittings. It depends on flow rate, pipe diameter, length and material. Friction rises sharply with higher flow in small pipes.

4. Pressure required at delivery

If water is delivered into a pressurised system or needs pressure at the outlet, add that pressure as head.

Total dynamic head (TDH)

TDH = lift from dynamic water level + elevation to delivery + friction losses + required pressure head

See TDH and flow rate.

Worked example

TDH = 65 + 9 + 6 + 5 = 85 m at 3 m³/h.

Reducing friction losses

Pressure for distribution

After the tank, water often flows by gravity. The pressure at each tap depends on the height of water in the tank above the tap minus friction losses in distribution pipes. See pressure and gravity flow from elevated tanks.

Common mistakes

How Quantum Geoconsultants can help

We calculate head and size pumps, pipelines and tanks together. See borehole pump installation and water tower construction.

Frequently asked questions

How many metres of head equal 1 bar?

About 10.2 metres of water head equals 1 bar of pressure.

Why include friction losses?

Water loses energy flowing through pipes and fittings. Long or narrow pipes can add many metres of head, which the pump must overcome.

Should I use static or dynamic water level?

Use the dynamic (pumping) water level, because that is where the pump lifts from during operation.

⚙️ Borehole pump size calculator

Enter your borehole's numbers from the test pumping report (or your best estimate) to see the total head, the flow and roughly how big a submersible pump or solar array you need.

0total head (m)
0pump flow (m³/hour)
0solar array (watts)

Rough planning figures only. Total head = pumping water level + tank height + an allowance for pipe friction. The final pump is chosen from the manufacturer's pump curves, your test pumping yield and your water quality.

Get a borehole pump installation quote

Send us your test pumping report, borehole depth and where the tank will sit. We will size the right submersible or solar pump and send a quotation for supply, installation and commissioning.

💬 WhatsApp